Density Test Report
Date :03/26/2025
Project No :2024C202
Client Company :CCG
Arrival Time :03/26/2025 08:00
Onsite Hours :
Name of the Project :Old Griffin Rd - Hawthorne Reserve
Project Location :Dallas
Weather :Clear sky
Departure Time :03/26/2025
ASEC Technician Name :Solomon Cherie
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 03/26/2025 | 1 | 25.7 | 96.5 | S-02 | 97.2 | 24.9 | 99.3 | 95 | D6938 | Pass |
| Location : | Lot #62, Elv/Depth :at finished subgrade | |||||||||
| Comment : | Gauge Serial No. :30942 | |||||||||
| 03/26/2025 | 2 | 27.9 | 90.6 | S-02 | 97.2 | 24.9 | 93.2 | 95 | D6938 | Fail |
| Location : | Lot #63, Elv/Depth :at finished subgrade | |||||||||
| Comment : | Recommended that his area be recompacted to achieve project specifications. | Gauge Serial No. :30942 | ||||||||
Technician Signature / DateSolomon Cherie, March 26, 2025
Reviewer Name / DateKenneth Mosman, April 30, 2025