- Density Test Report Report ID: 80058
- This project is inactive from admin. Download Report
Density Test Report
Date :03/27/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :03/27/2025 9:00
Onsite Hours :07:30
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :sunny
Departure Time :03/27/2025 16:30
ASEC Technician Name :Aminullah Azimi
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 03/27/2025 | 1 | 17.4 | 112.8 | 2025-008 SP | 115.7 | 14.7 | 97.5 | 95 | D6938 | Pass |
| Location : | Lot #137, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 03/27/2025 | 2 | 16.5 | 111.0 | 2025-008 SP | 115.7 | 14.7 | 95.9 | 95 | D6938 | Pass |
| Location : | Lot #138, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | need proctor for result | Gauge Serial No. :85759 | ||||||||
| 03/27/2025 | 3 | 17.2 | 111.0 | 2025-008 SP | 115.7 | 14.7 | 95.9 | 95 | D6938 | Pass |
| Location : | Lot #139, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
Technician Signature / DateAminullah Azimi, March 27, 2025
Reviewer Name / DateKenneth Mosman, April 30, 2025