Density Test Report

Date :04/18/2025
Project No :2024C213
Client Company :WDG
Arrival Time :04/18/2025 8:00
Onsite Hours :07:30
Name of the Project :Covington Town Center PH II
Project Location :Covington, GA
Weather :sunny
Departure Time :04/18/2025 15:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/18/2025 1 17.8 104.0 ASECP001 106.0 18.2 98.1 95 D6938 Pass
Location : water storm trench, 31 feet east from MHB1, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
04/18/2025 2 17.3 96.6 2025-017 SP 99.0 18.3 97.6 95 D6938 Pass
Location : water storm trench between MHB1 and MHB2, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
04/18/2025 3 16.9 104.4 ASECP001 106.0 18.2 98.5 98 D6938 Pass
Location : water storm trench, 42 feet SE from MHB1., Elv/Depth :0.5 foot below finished grade
Comment : Gauge Serial No. :85759
04/18/2025 4 17.9 115.2 2025-017 SP 99.0 18.3 98.7 95 D6938 Pass
Location : service line in the front of building , Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
04/18/2025 5 17.6 104.8 ASECP001 106.0 18.2 98.9 98 D6938 Pass
Location : building pad , Elv/Depth :at finished grade
Comment : Gauge Serial No. :85759
04/18/2025 6 18 115.2 2025-017 SP 99.0 18.3 98.6 98 D6938 Pass
Location : building pad, Elv/Depth :at finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, April 18, 2025
Reviewer Name / DateKenneth Mosman, May 07, 2025