Skip to content

Density Test Report

Date :05/23/2025
Project No :2025C146
Client Company :Davidson Homes, LLC
Arrival Time :05/23/2025 13:00
Onsite Hours :
Name of the Project :Greene Farms Subdivision
Project Location :1451 Highway 113, Cartersville, Georgia
Weather :
Departure Time :05/23/2025
ASEC Technician Name :Solomon Cherie

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/23/2025 1 29.8 95.5 ASECP002 99.4 22.4 96.1 95 D6938 Pass
Location : Lot #16, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 2 20.3 90.6 ASECP002 99.4 22.4 91.1 95 D6938 Fail
Location : Lot #17, Elv/Depth :5 feet below finished grade
Comment : Failed, Grading For man is informed to fix. Gauge Serial No. :30942
05/23/2025 3 26.1 94.8 ASECP002 99.4 22.4 95.4 95 D6938 Pass
Location : Lot #18, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 4 23.8 95.0 ASECP002 99.4 22.4 95.6 95 D6938 Pass
Location : Lot #19, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 5 23.9 97.6 ASECP002 99.4 22.4 98.2 95 D6938 Pass
Location : Lot #20, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 6 16.1 109.5 ASECP005 106.8 16.5 102.5 95 D6938 Pass
Location : Lot #21, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 7 21.1 104.0 ASECP003 109.2 18.5 95.2 95 D6938 Pass
Location : Lot #23, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 8 17.6 110.6 ASECP005 106.8 16.5 103.6 95 D6938 Pass
Location : Lot #24, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 9 17.1 107.4 ASECP005 106.8 16.5 100.6 95 D6938 Pass
Location : Lot #25, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 10 12 117.3 ASECP004 115.0 12.0 102.0 95 D6938 Pass
Location : Lot #26, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 11 16.3 109.2 ASECP003 109.2 18.5 100.0 95 D6938 Pass
Location : Lot #27, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 12 23 97.7 ASECP002 99.4 22.4 98.3 95 D6938 Pass
Location : Lot #28, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 13 15.8 112.9 ASECP004 115.0 12.0 98.2 95 D6938 Pass
Location : Lot #29, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
05/23/2025 14 18 104.2 ASECP005 106.8 16.5 97.6 95 D6938 Pass
Location : Lot #30, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :30942
Technician Signature / DateSolomon Cherie, May 23, 2025
Reviewer Name / DateKenneth Mosman, June 09, 2025