Density Test Report

Date :04/03/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :04/03/2025 09:30
Onsite Hours :07:30
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Sunny
Departure Time :04/03/2025 17:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/03/2025 1 22.1 101.0 2025-011 SP 115.0 15.5 87.8 95 D2937 Fail
Location : Lot #121, Elv/Depth :8 feet below finished grade
Comment : In-situ moisture contents well above optimum moisture. Recommended scarification, aeration and recompaction.
04/03/2025 2 20.9 102.7 2025-011 SP 115.0 15.5 89.3 95 D2937 Fail
Location : Lot #121, Elv/Depth :8 feet below finished grade
Comment : In-situ moisture contents well above optimum moisture. Recommended scarification, aeration and recompaction.
04/03/2025 3 23.0 0.0 2025-011 SP 115.0 15.5 0.0 D2937 Pass
Location : Lot #120, Elv/Depth :8 feet below finished grade
Comment : Moisture content check
04/03/2025 4 20.2 0.0 2025-011 SP 115.0 15.5 0.0 D2937 Pass
Location : Lot #119, Elv/Depth :8 feet below finished grade
Comment : Moisture content check
04/03/2025 5 23.6 0.0 2025-011 SP 115.0 15.5 0.0 D2937 Pass
Location : West of entrance, Elv/Depth :
Comment : Moisture content check
04/03/2025 6 18.1 0.0 2025-011 SP 115.0 15.5 0.0 D2937 Pass
Location : Lot #38, Elv/Depth :8 feet below finished grade
Comment : Moisture content check
04/03/2025 7 19.2 0.0 2025-011 SP 115.0 15.5 0.0 D2937 Pass
Location : Lot #119, Elv/Depth :8 feet below finished grade
Comment : Moisture content check
Technician Signature / DateSean Willett, April 3, 2025
Reviewer Name / DateKenneth Mosman, June 23, 2025