Density Test Report

Date :05/22/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :05/22/2025 10:00
Onsite Hours :02:00
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Sunny
Departure Time :05/22/2025 12:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/22/2025 1 25.2 94.1 2025-012 SP 105.6 18.9 89.1 98 D2937 Fail
Location : Lot #80, Elv/Depth :at finished grade
Comment : In-situ moisture contents much higher than optimum moisture. Recommend scarify, aerate and recompact.
05/22/2025 2 20.8 100.7 2025-012 SP 105.6 18.9 95.4 98 D2937 Fail
Location : Lot #81, Elv/Depth :at finished grade
Comment :
Technician Signature / DateSean Willett, May 22, 2025
Reviewer Name / DateKenneth Mosman, June 23, 2025