Density Test Report

Date :08/21/2025
Project No :2025C215
Client Company :Artisan
Arrival Time :08/21/2025 9:00
Onsite Hours :08:30
Name of the Project :NW Unit 4 Parkway Ext. Phase 1
Project Location :Dallas
Weather :sunny
Departure Time :08/21/2025 17:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
08/21/2025 1 21.9 92.0 2025-032 SP 94.9 25.0 96.9 95 D6938 Pass
Location : Sewer trench 19 feet to the east of MH9, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :30942
08/21/2025 2 18.1 96.1 2025-031 SP 101.0 20.7 95.1 95 D6938 Pass
Location : Sewer trench 110 feet to the east of MH9, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :30942
08/21/2025 3 23.5 90.9 2025-032 SP 94.9 25.0 95.8 95 D6938 Pass
Location : Sewer trench 115 feet to the west of MH8, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :30942
08/21/2025 4 23.2 114.7 2025-032 SP 94.9 25.0 98.1 98 D6938 Pass
Location : Sewer trench 14 feet to the west of MH8, Elv/Depth :at finished grade
Comment : Gauge Serial No. :30942
08/21/2025 5 22.7 112.4 2025-032 SP 94.9 25.0 96.5 95 D6938 Pass
Location : Sewer trench 13 feet to the east of MH8, Elv/Depth :at finished grade
Comment : Gauge Serial No. :30942
08/21/2025 6 18 113.4 2025-031 SP 101.0 20.7 95.1 95 D6938 Pass
Location : Lot #14, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :30942
08/21/2025 7 28.3 83.4 2025-031 SP 101.0 20.7 82.6 95 D6938 Fail
Location : Lot #17, Elv/Depth :at finished grade
Comment : This test failed due to its moisture level being higher than specified. Gauge Serial No. :30942
08/21/2025 8 29.1 81.3 2025-031 SP 101.0 20.7 80.5 95 D6938 Fail
Location : Lot #18, Elv/Depth :at finished grade
Comment : This test failed due to moisture levels being higher than specified Gauge Serial No. :30942
08/21/2025 9 14 100.4 2025-031 SP 101.0 20.7 99.4 95 D6938 Pass
Location : Lot #15, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :30942
08/21/2025 10 18 113.4 2025-031 SP 101.0 20.7 95.1 95 D6938 Pass
Location : Sewer trench 93 feet to the east of MH8, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :30942
08/21/2025 11 22.1 91.6 2025-032 SP 94.9 25.0 96.5 95 D6938 Pass
Location : Sewer trench 145 feet to the east of MH8, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :30942
Technician Signature / DateAminullah Azimi, August 21, 2025
Reviewer Name / DateKenneth Mosman, September 12, 2025