Density Test Report

Date :10/13/2025
Project No :2025C245
Client Company :Bearing Engineering
Arrival Time :10/13/2025 07:00
Onsite Hours :11:00
Name of the Project :Dunkin Donuts 2025
Project Location :US 29, Palmetto, GA
Weather :Sunny
Departure Time :10/13/2025 18:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
10/13/2025 1 21.3 90.8 3 94.7 25.3 95.9 95 D6938 Pass
Location : testing location #3 retaining wall, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
10/13/2025 2 20.5 88.0 3 94.7 25.3 92.9 95 D6938 Fail
Location : testing location #2 retaining wall, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture content well below optimum moisture. Recompaction required. Gauge Serial No. :77-19952
10/13/2025 3 20.5 93.9 3 94.7 25.3 99.2 95 D6938 Pass
Location : testing location #1 retaining wall, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/13/2025 4 22.1 87.4 3 94.7 25.3 92.3 95 D6938 Fail
Location : testing location #2 retaining wall, Elv/Depth :2 feet below finished grade
Comment : Retest of previous failing test. Recompaction required. Gauge Serial No. :77-19952
10/13/2025 5 19.1 98.2 3 94.7 25.3 103.7 95 D6938 Pass
Location : testing location #2 retaining wall, Elv/Depth :2 feet below finished grade
Comment : Retest Gauge Serial No. :77-19952
10/13/2025 6 23.9 71.8 3 94.7 25.3 75.8 95 D6938 Fail
Location : Roadway in front of retaining wall, Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/13/2025 7 21.3 79.4 3 94.7 25.3 83.8 95 D6938 Fail
Location : roadway in front of retaining wall, Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/13/2025 8 19.4 91.7 3 94.7 25.3 96.8 95 D6938 Pass
Location : roadway in front of retaining wall, Elv/Depth :3 feet below finished grade
Comment : Retest Gauge Serial No. :77-19952
10/13/2025 9 22.8 79.3 3 94.7 25.3 83.7 95 D6938 Fail
Location : roadway in front of retaining wall, Elv/Depth :3 feet below finished grade
Comment : Retest Gauge Serial No. :77-19952
10/13/2025 10 20.2 93.0 3 94.7 25.3 98.2 95 D6938 Pass
Location : roadway in front of wall, Elv/Depth :3 feet below finished grade
Comment : Retest Gauge Serial No. :77-19952
10/13/2025 11 21.3 87.2 3 94.7 25.3 92.1 95 D6938 Fail
Location : testing location #2 retaining wall, Elv/Depth :at finished grade
Comment : Reompaction required. Gauge Serial No. :77-19952
10/13/2025 12 21.1 90.3 3 94.7 25.3 95.4 95 D6938 Pass
Location : testing location #1 retaining wall, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
10/13/2025 13 22.5 91.5 3 94.7 25.3 96.6 95 D6938 Pass
Location : testing location #2 retaining wall, Elv/Depth :at finished grade
Comment : Retest Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, October 13, 2025
Reviewer Name / DateKenneth Mosman, October 14, 2025