- Concrete Test Report Report ID: 89941
- Edit Download Report
Concrete Test Report
Date :01/29/2026
Project No :2025C280
Client Company :WSP
Arrival Time :01/29/2026 10:00
Onsite Hours :03:00
Name of the Project :Lee Road
Project Location :Douglasville
Weather :Overcast
Departure Time :01/29/2026 13:00
ASEC Technician Name :Mahendra Mylabathula
Concrete Placement Information
Location(S):
N/A
Testing:
1 Set of concrete specimens (5 per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The specimen will remain on site for the initial 24-48 hrs curing.
Compliance:
Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)
Deviations and/or noncompliances were noted during the field placement (refer to remarks below)
Specimen
Pick Up: 1 Sets of concrete specimens/ 5 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Pick Up: 1 Sets of concrete specimens/ 5 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing:
Specimen were stored for the initial 24 hours.
Near the poured structure
In an insulated curing box
Other
Remarks:
Field Test Data
Specimen Type Selection : Cylinder
Set Number :2026-016
Date Sampled :01/29/2026
Sampled By :Mahendra Mylabathula
Contractor :Curb and Gutter Contracting Co.
Truck Number :2489
Time Batched :11:22
Location of Placement :Sidewalk on Lee Road
Number of samples cast :5
Ambient Temperature (°f) :40
Slump (in.) :3.5
Water added (gal.) :N/A
Laboratory Number :2026-016
Time Sampled :12:20
Weather Condition :Overcast
Concrete Supplier :Thomas
Mix ID :139651
Quantity of Load (cu. yd.) :9
Sample Cast :1
Specified Strength :N/A
Concrete Temperature(°f) :50
Air Content (%) :5
Unit Weight (pcf) :15.1
Strength Test Results
| Specimen Number | Scheduled Test Date | Date Tested | Age (days) | Dia(in.) | Area (sq in.) | Maximum Loads (lbf) | Strength (lbs) | % Design Strength | Type of Fracture |
|---|---|---|---|---|---|---|---|---|---|
| A | 02/05/2026 | 02/05/2026 | 7 | 3.93 | 12.15 | 31078 | 2560 | Infinity | Type 5 |
| B | 02/26/2026 | 02/26/2026 | 28 | 3.90 | 11.95 | 44730 | 3740 | Infinity | Type 2 |
| C | 02/26/2026 | 02/26/2026 | 28 | 3.90 | 11.95 | 47670 | 3990 | Infinity | Type 2 |
| D | 02/26/2026 | 02/26/2026 | 28 | 3.90 | 11.95 | 47634 | 3990 | Infinity | Type 2 |
| E | 03/26/2026 | 03/26/2026 | 55 | 3.90 | 11.95 | 56913 | 4760 | Infinity | Type 2 |
UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.
(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed
Technician Signature / DateCatherine Lanier, January 29, 2026
Reviewer Name / DateKenneth Mosman, April 08, 2026