Density Test Report

Date :02/06/2026
Project No :2026C103
Client Company :Artisan
Arrival Time :02/06/2026 08:00
Onsite Hours :9:30
Name of the Project :NW PH 2, UNIT 4
Project Location :Dallas
Weather :sunny
Departure Time :02/06/2026 17:30
ASEC Technician Name :Clyde Smith

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/06/2026 1 15.9 97.0 Field proctor #6 98.0 17.2 99.0 95 D6938 Pass
Location : Building Lots #61 and 62, Elv/Depth :884
Comment : Gauge Serial No. :91643
02/06/2026 2 16.8 96.1 Field proctor #6 98.0 17.2 98.1 95 D6938 Pass
Location : Building Lots #61 and 62, Elv/Depth :884
Comment : Gauge Serial No. :91643
02/06/2026 3 12.2 105.1 2025-035 SP 107.8 13.0 97.5 D6938 Pass
Location : Building Lots #61 and 62 , Elv/Depth :885
Comment : Gauge Serial No. :91643
02/06/2026 4 15.4 96.9 Field proctor #6 98.0 17.2 98.9 95 D6938 Pass
Location : Building Lots #57 and 58, Elv/Depth :875
Comment : Gauge Serial No. :91643
02/06/2026 5 15.9 101.1 2025-033 SP 104.0 16.2 97.2 95 D6938 Pass
Location : Building Lots #57 and 58, Elv/Depth :876
Comment : Gauge Serial No. :91643
Technician Signature / DateClyde Smith, February 6, 2026
Reviewer Name / DateKenneth Mosman, February 18, 2026