Daily Field Report

Date :03/25/2026
Project No :2025C186
Client Company :CWM
Arrival Time :03/25/2026
Onsite Hours :
Name of the Project :Tom B. David Airport - Rehab Parallel Taxiway & Terminal Apron
Project Location :Calhoun
Weather :overcast
Departure Time :03/25/2026
ASEC Technician Name :Russell Hendrix

Observations/Finding

As requested, the site was visited by our AS Engineering and Consulting (ASEC) representative for the purpose of providing quality control inspection and testing services. Visual observation techniques were employed to verify compliance with project drawing/specifications, applicable codes, and materials submittals. The following observations were observed on site this day:

It was observed prior to the installation of the 18-inch storm drain along the future Taxiway A4 alignment that approximately 12 inches of No. 57 stone was placed continuously along the entire pipe bedding. Installation of the 18-inch reinforced concrete pipe (RCP) included the use of rubber gaskets and pipe lubricant to for proper joint sealing (see photos). Pipe placement progressed in a north-to-south direction.

A proof-roll was performed on the Taxiway A3 square extension area from Station 40+00 to Station 41+00 using a loaded tandem axle dump truck. Representatives from UES, ASEC, and C.W. Matthews Contracting Co. were present during testing.  During the proof-roll, subgrade instability was observed, including rutting and pumping, consistent with previously documented conditions. Based on these observations, UES recommended the same remediation approach as previously established. This includes placement of geotextile fabric over the subgrade, followed by 12 inches of No. 4 stone, and an additional 12 inches of Graded Aggregate Base (GAB) to support future asphalt paving.

Geotextile fabric was installed in the subject area (see photos); however, placement of the No. 4 stone was not completed on this date (see photo).

No further observations were made.

18 inch storm drain facing south

Delivery ticket

Geo fabric placed

#4s placed

Proof roll

Storm Drain placed

Bedding for Storm drain placed

Fabric placed

18 inch storm drain placed

rubber seal and lubricant used on 18 inch RCP

Lubricant for 18 inch storm drain

Rubber seals and 18 inch storm drain

Storm drain undercutting

Storm drain undercutting

Technician Signature / DateRussell Hendrix, March 25, 2026
Reviewer Name / DateKenneth Mosman, March 31, 2026