Density Test Report

Date :04/20/2026
Project No :2026C125
Client Company :Lewis Contracting
Arrival Time :04/20/2026 14:00
Onsite Hours :02:00
Name of the Project :Pittman Park - Garibaldi St. Stormwater
Project Location :Atlanta
Weather :Sunny
Departure Time :04/20/2026 16:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/20/2026 1 17.8 100.6 Proctor 1 104.9 19.8 95.9 98 D6938 Fail
Location : Storm line in parking lot, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
04/20/2026 2 15.1 100.1 Proctor 1 104.9 19.8 95.4 98 D6938 Fail
Location : Storm line in parking lot, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, April 20, 2026
Reviewer Name / DateKenneth Mosman, April 27, 2026