Concrete Test Report

Date :05/29/2026
Project No :2025C214
Client Company :Artisan
Arrival Time :05/29/2026
Onsite Hours :
Name of the Project :NW Unit 4 BRIDGE (Materials Testing)
Project Location :Dallas
Weather :Sunny
Departure Time :05/29/2026
ASEC Technician Name :Sean Willett

Concrete Placement Information

Location(S): N/A
Testing: 5 Set of concrete specimens (7 per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The specimen will remain on site for the initial 24-48 hrs curing.
Compliance:

Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)

Deviations and/or noncompliances were noted during the field placement (refer to remarks below)

Specimen
Pick Up:
5 Sets of concrete specimens/ 7 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing: Specimen were stored for the initial 24 hours.
Near the poured structure
In an insulated curing box
Other
Remarks:

Field Test Data

Specimen Type Selection : Cylinder

Set Number :A
Date Sampled :05/29/2026
Sampled By :Sean Willett
Contractor :RWS
Truck Number :474
Time Batched :06:02
Location of Placement :Wall for bridge
Number of samples cast :7
Ambient Temperature (°f) :70
Slump (in.) :8.5
Water added (gal.) :N/A
Laboratory Number :N/A
Time Sampled :07:06
Weather Condition :Sunny
Concrete Supplier :Ernest
Mix ID :40CA6
Quantity of Load (cu. yd.) :9
Sample Cast :5
Specified Strength :4000 AEA
Concrete Temperature(°f) :75
Air Content (%) :3.5
Unit Weight (pcf) :141.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 N/A
2 N/A
3 N/A
4 N/A
5 N/A
6 N/A
7 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :B
Date Sampled :05/29/2026
Sampled By :Sean Willett
Contractor :RWS
Truck Number :490
Time Batched :07:14
Location of Placement :Wall for bridge
Number of samples cast :7
Ambient Temperature (°f) :71
Slump (in.) :5
Water added (gal.) :N/A
Laboratory Number :N/A
Time Sampled :08:13
Weather Condition :Sunny
Concrete Supplier :Ernest
Mix ID :40CA6
Quantity of Load (cu. yd.) :54
Sample Cast :5
Specified Strength :4000 AEA
Concrete Temperature(°f) :77
Air Content (%) :3.0
Unit Weight (pcf) :145.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 N/A
2 N/A
3 N/A
4 N/A
5 N/A
6 N/A
7 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :C
Date Sampled :05/29/2026
Sampled By :Sean Willett
Contractor :RWS
Truck Number :467
Time Batched :08:52
Location of Placement :Wall for bridge
Number of samples cast :7
Ambient Temperature (°f) :72
Slump (in.) :4.5
Water added (gal.) :N/A
Laboratory Number :N/A
Time Sampled :09:35
Weather Condition :Sunny
Concrete Supplier :Ernest
Mix ID :40CA6
Quantity of Load (cu. yd.) :126
Sample Cast :5
Specified Strength :4000 AEA
Concrete Temperature(°f) :76
Air Content (%) :3.5
Unit Weight (pcf) :147.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 N/A
2 N/A
3 N/A
4 N/A
5 N/A
6 N/A
7 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :D
Date Sampled :05/29/2026
Sampled By :Sean Willett
Contractor :RWS
Truck Number :474
Time Batched :09:12
Location of Placement :Wall for bridge
Number of samples cast :7
Ambient Temperature (°f) :75
Slump (in.) :7.5
Water added (gal.) :N/A
Laboratory Number :N/A
Time Sampled :10:22
Weather Condition :Sunny
Concrete Supplier :Ernest
Mix ID :40CA6
Quantity of Load (cu. yd.) :153
Sample Cast :5
Specified Strength :4000 AEA
Concrete Temperature(°f) :77
Air Content (%) :3.5
Unit Weight (pcf) :146.4

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 N/A
2 N/A
3 N/A
4 N/A
5 N/A
6 N/A
7 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :E
Date Sampled :05/29/2026
Sampled By :Sean Willett
Contractor :RWS
Truck Number :306
Time Batched :10:05
Location of Placement :Wall for bridge
Number of samples cast :7
Ambient Temperature (°f) :76
Slump (in.) :4.5
Water added (gal.) :N/A
Laboratory Number :N/A
Time Sampled :11:15
Weather Condition :Sunny
Concrete Supplier :Ernest
Mix ID :40CA6
Quantity of Load (cu. yd.) :207
Sample Cast :5
Specified Strength :4000 AEA
Concrete Temperature(°f) :80
Air Content (%) :2.5
Unit Weight (pcf) :144.4

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 N/A
2 N/A
3 N/A
4 N/A
5 N/A
6 N/A
7 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Technician Signature / DateSean Willett, May 29, 2026
Reviewer Name / DateKenneth Mosman, June 26, 2026