Density Test Report

Date :09/22/2026
Project No :2026C101
Client Company :Artisan
Arrival Time :09/22/2026 07:30
Onsite Hours :10:00
Name of the Project :Seven Hills PHASE 13, UNIT 3 Lots
Project Location :Dallas
Weather :Sunny
Departure Time :09/22/2026 17:30
ASEC Technician Name :Clyde Smith

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/22/2026 1 19.2 99.6 2025-033 SP 104.0 16.2 95.8 95 D6938 Pass
Location : Roadway between Z18 and Z20, Elv/Depth :6 feet below finished grade
Comment : Gauge Serial No. :91643
09/22/2026 2 17.3 102.5 2025-033 SP 104.0 16.2 98.6 95 D6938 Pass
Location : Roadway between Z18 and Z20, Elv/Depth :6 feet below finished grade
Comment : Gauge Serial No. :91643
09/22/2026 3 24.9 113.8 2025-032 SP 94.9 25.0 96.0 95 D6938 Pass
Location : Roadway between Z18 and Z20, Elv/Depth :6 feet below finished grade
Comment : Gauge Serial No. :91643
09/22/2026 4 19.9 90.2 2025-032 SP 94.9 25.0 95.0 95 D6938 Fail
Location : Roadway between Z18 and Z20, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :91643
09/22/2026 5 19.1 92.7 2025-032 SP 94.9 25.0 97.7 95 D6938 Pass
Location : Roadway between Z18 and Z20, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :91643
09/22/2026 6 13.3 102.3 2025-033 SP 104.0 16.2 98.4 98 D6938 Pass
Location : Building Lot # 10, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :91643
09/22/2026 7 14.4 101.9 2025-033 SP 104.0 16.2 98.0 98 D6938 Fail
Location : Building Lot #10, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :91643
Technician Signature / DateClyde Smith, September 22, 2026
Reviewer Name / DateKenneth Mosman, October 21, 2026