Density Test Report

Date :08/29/2021
Project No :2021C070
Client Company :CCG Constructors LLC (Century)
Arrival Time :08/27/2021 09:15
Onsite Hours :05:00
Name of the Project :Harmony Heights
Project Location :Mt. Olive Road at Brentwood Drive, Commerce, GA
Weather :sunny
Departure Time :08/27/2021 14:15
ASEC Technician Name :Russell Hendrix

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
08/27/2021 1 20.7 90.4 P-01 102.0 16.6 88.6 90 D6938 Fail
Location : Center (2nd phase), Elv/Depth :
Comment : Gauge Serial No. :29588
08/27/2021 2 22.3 91.9 P-01 102.0 16.6 90.1 90 D6938 Pass
Location : Center (2nd phase) , Elv/Depth :
Comment : Gauge Serial No. :29588
08/27/2021 3 20 95.8 P-01 102.0 16.6 93.9 90 D6938 Pass
Location : Center (2nd phase), Elv/Depth :
Comment : Gauge Serial No. :29588
4 19.1 92.1 P-01 102.0 16.6 90.3 90 D6938 Pass
Location : Center (2nd phase), Elv/Depth :
Comment : This was a retest of #1 after compactor had re-compacted same area 20 times without adding soil. Suspect new proctor needed. Gauge Serial No. :29588
Technician Signature / DateRussell Hendrix, August 29, 2021
Reviewer Name / DateRamchandra Mogulla, November 07, 2021