Daily Field Report

Date :01/25/2022
Project No :2021C060
Client Company :Pulte Group
Arrival Time : 02:30
Onsite Hours :
Name of the Project :Suncity - Peachtree
Project Location :Griffin, GA
Weather :
Departure Time :01/25/2022 05:00
ASEC Technician Name :Jamal Geathers

Observations/Finding

The site was visited by the undersigned AS Engineering and Consulting (ASEC) representative for the purpose of providing quality control inspection and testing services. Visual observation techniques were employed to verify compliance with project drawings/specifications, applicable codes, and materials submittals.

The ASEC representative performed Dynamic Cone Penetrometer (DCP) tests one the below referenced footing areas.  All referenced footings were found to meet job specification for a soil bearing pressure of 2,500 psf.

A reinforcing steel inspection was performed on the following locations: (Lots #6, 7, and 41).  Reinforcing steel was observed to meet job specifications for required size, spacing, lap and cover. No discrepancies were noted.

If foundation soils become wet prior to concrete placement, they should be reevaluated by a geotechnical engineer or qualified soils technician. All loose fall-in soils or debris should be removed from foundations prior to concrete placement.

DCP TEST DATA SHEET
Project Name: Suncity- Peachtree Date: January 25
Project Number: 2021C060 Technician: Jamal Geathers
Project Location: Griffin, Ga
DCP LOCATION:
Lot #, North/South/Center etc
Lot 7 (Front of lot) DCP LOCATION:
Lot #, North/South/Center etc
Lot 7 (back of lot)
Depth
(feet)
Set
2″
N
1.75″
Description Depth
(feet)
Set
2″
N
1.75″
Description
1 9 11 1 8 11
2 9 12 2 8 10
3 9 10 3 8 9
4 9 1o 4 8 8
5 5
6 6
7 7
8 8
9 9
10 10
jrg
DCP LOCATION:
Lot #, North/South/Center etc
Lot 6 (front of lot) DCP LOCATION:
Lot #, North/South/Center etc
lot 10 back of lot
Depth
(feet)
Set
2″
N
1.75″
Description Depth
(feet)
Set
2″
N
1.75″
Description
1 8 7 1 8 9
2 8 11 2 8 12
3 8 12 3 8 13
4 8 18 4 8 12
5 5
6 6
7 7
8 8
9 9
10 10

 

DCP TEST DATA SHEET
Project Name: Suncity- Peachtree Date: January 25
Project Number: 2021C060 Technician: Jamal Geathers
Project Location: Griffin, Ga
DCP LOCATION:
Lot #, North/South/Center etc
Lot 41 (left side of Lot) DCP LOCATION:
Lot #, North/South/Center etc
Lot 41( Back of lot)
Depth
(feet)
Set
2″
N
1.75″
Description Depth
(feet)
Set
2″
N
1.75″
Description
1 9 16 1 8 18
2 9 15 2 8 16
3 9 auger refusal 3 8 14
4 9 4 8 17
5 5
6 6

 

Technician Signature / DateJamal Geathers, January 25, 2022
Reviewer Name / DateKenneth Mosman, February 15, 2022