Density Test Report

Date :03/09/2022
Project No :2021C082
Client Company :CCG Constructors LLC (Century)
Arrival Time :02/16/2022
Onsite Hours :
Name of the Project :Estates at Old Friendship
Project Location :Buford, GA
Weather :40 Cloudy
Departure Time :02/16/2022
ASEC Technician Name :Russell Hendrix

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/16/2022 1 15.5 83.9 P-1 109.6 15.7 76.6 95 D6938 Fail
Location : Proposed road Friendship Creek Drive (Sta 5+00), Elv/Depth :1063
Comment : Recompaction necessary Gauge Serial No. :38069
02/16/2022 2 15.3 89.7 P-1 109.6 15.7 81.8 95 D6938 Fail
Location : Friendship Creek Drive (Sta 4+00), Elv/Depth :1063
Comment : Recompaction necessary Gauge Serial No. :38069
02/16/2022 3 17.7 85.1 P-1 109.6 15.7 77.6 95 D6938 Fail
Location : Main road (Sta 16+50), Elv/Depth :1081
Comment : Recompaction necessary Gauge Serial No. :38069
02/16/2022 4 15.5 84.5 P-1 109.6 15.7 77.1 95 D6938 Fail
Location : Main road (Sta 15+50), Elv/Depth :1081
Comment : Recompaction necessary Gauge Serial No. :38069
Technician Signature / DateRussell Hendrix, March 9, 2022
Reviewer Name / DateKenneth Mosman, February 16, 2023