- Density Test Report Report ID: 54555
- This project is inactive from admin.Download Report
Density Test Report
Date :09/02/2022
Project No :2022C128
Client Company :Century
Arrival Time :09/02/2022 12:00
Onsite Hours :02:30
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Cloudy with Scattered Showers
Departure Time :09/02/2022 14:30
ASEC Technician Name :Vidal Dias
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
09/02/2022 | 1 | 24.9 | 89.2 | 3 | 102.3 | 20.2 | 87.2 | 95 | D6938 | Fail |
Location : | see field report for locations, Elv/Depth :+1180 | |||||||||
Comment : | See field report for remarks | Gauge Serial No. : | ||||||||
09/02/2022 | 2 | 31.1 | 88.5 | 3 | 102.3 | 20.2 | 86.5 | 95 | D6938 | Fail |
Location : | , Elv/Depth :+1180 | |||||||||
Comment : | See field report for remarks | Gauge Serial No. : | ||||||||
09/02/2022 | 3 | 24.7 | 94.2 | 3 | 102.3 | 20.2 | 92.1 | 95 | D6938 | Fail |
Location : | , Elv/Depth :+1180 | |||||||||
Comment : | See field report for remarks | Gauge Serial No. : |
Technician Signature / DateVidal Dias, September 2, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022