Density Test Report

Date :09/02/2022
Project No :2022C128
Client Company :Century
Arrival Time :09/02/2022 12:00
Onsite Hours :02:30
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Cloudy with Scattered Showers
Departure Time :09/02/2022 14:30
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/02/2022 1 24.9 89.2 3 102.3 20.2 87.2 95 D6938 Fail
Location : see field report for locations, Elv/Depth :+1180
Comment : See field report for remarks Gauge Serial No. :
09/02/2022 2 31.1 88.5 3 102.3 20.2 86.5 95 D6938 Fail
Location : , Elv/Depth :+1180
Comment : See field report for remarks Gauge Serial No. :
09/02/2022 3 24.7 94.2 3 102.3 20.2 92.1 95 D6938 Fail
Location : , Elv/Depth :+1180
Comment : See field report for remarks Gauge Serial No. :
Technician Signature / DateVidal Dias, September 2, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022