Density Test Report

Date :09/08/2022
Project No :2022C128
Client Company :Century
Arrival Time :09/08/2022 11:00
Onsite Hours :03:30
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Cloudy
Departure Time :09/08/2022 14:30
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/08/2022 Test 1 27.9 90.2 2 92.8 22.3 97.2 98 D6938 Fail
Location : Final grade of first section , Elv/Depth :
Comment : Gauge Serial No. :
09/08/2022 Test 2 23.8 93.1 2 92.8 22.3 100.3 98 D6938 Pass
Location : Final grade of first section , Elv/Depth :
Comment : Gauge Serial No. :
09/08/2022 test 3 17.8 100.7 2 92.8 22.3 108.5 95 D6938 Pass
Location : Lift one of second section , Elv/Depth :
Comment : Gauge Serial No. :
Technician Signature / DateVidal Dias, September 8, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022