- Density Test Report Report ID: 54619
- This project is inactive from admin.Download Report
Density Test Report
Date :09/12/2022
Project No :2022C128
Client Company :Century
Arrival Time :09/12/2022 11:00
Onsite Hours :02:00
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Clear
Departure Time :09/12/2022 13:00
ASEC Technician Name :Vidal Dias
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
09/12/2022 | Test 1 | 18 | 91.3 | 2 | 92.8 | 22.3 | 98.4 | 95 | D6938 | Pass |
Location : | see Daily Field report, Elv/Depth : | |||||||||
Comment : | Gauge Serial No. : |
Technician Signature / DateVidal Dias, September 12, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022