Density Test Report

Date :09/27/2022
Project No :2022C128
Client Company :Century
Arrival Time :09/27/2022 13:00
Onsite Hours :02:00
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Sunny
Departure Time :09/27/2022 15:00
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/27/2022 Test 1 17.0 99.8 2 92.8 22.3 107.5 95 D6938 Pass
Location : Wall 3, Elv/Depth :
Comment : Gauge Serial No. :
09/27/2022 Test 2 19.6 99.9 3 102.3 20.2 97.7 95 D6938 Pass
Location : Wall 3, Elv/Depth :
Comment : Gauge Serial No. :
Technician Signature / DateVidal Dias, September 27, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022