- Density Test Report Report ID: 54918
- This project is inactive from admin.Download Report
Density Test Report
Date :10/03/2022
Project No :2022C128
Client Company :Century
Arrival Time :10/03/2022 09:00
Onsite Hours :06:00
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Sunny
Departure Time :10/03/2022 15:00
ASEC Technician Name :Vidal Dias
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
10/03/2022 | 1 | 13.9 | 112.5 | 1 | 104.7 | 17.9 | 94.4 | 95 | D6938 | Fail |
Location : | Wall #3 , Elv/Depth :+1180 | |||||||||
Comment : | Gauge Serial No. : | |||||||||
10/03/2022 | 2 | 12.9 | 113.0 | 1 | 100 | 20.3 | 113.0 | 95 | D6938 | Pass |
Location : | North east section of wall, Elv/Depth :+1180 | |||||||||
Comment : | retest of Test 1 | Gauge Serial No. : |
Technician Signature / DateVidal Dias, October 3, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022