Density Test Report

Date :10/03/2022
Project No :2022C128
Client Company :Century
Arrival Time :10/03/2022 09:00
Onsite Hours :06:00
Name of the Project :Sidney Square, Flowery Branch
Project Location :Flowery Branch
Weather :Sunny
Departure Time :10/03/2022 15:00
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
10/03/2022 1 13.9 112.5 1 104.7 17.9 94.4 95 D6938 Fail
Location : Wall #3 , Elv/Depth :+1180
Comment : Gauge Serial No. :
10/03/2022 2 12.9 113.0 1 100 20.3 113.0 95 D6938 Pass
Location : North east section of wall, Elv/Depth :+1180
Comment : retest of Test 1 Gauge Serial No. :
Technician Signature / DateVidal Dias, October 3, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022