Density Test Report

Date :11/04/2022
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :11/04/2022 12:00
Onsite Hours :03:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :Sunny
Departure Time :11/04/2022 15:00
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
11/04/2022 1 19.8 119.7 1 83.2 25.3 120.1 95 D6938 Pass
Location : , Elv/Depth :1187
Comment : Different material from the Moisture-Density Relationship on file. Sample retrieved to run new proctor. Gauge Serial No. :
Technician Signature / DateVidal Dias, November 4, 2022
Reviewer Name / DateKenneth Mosman, April 07, 2023