Density Test Report

Date :11/08/2022
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :11/08/2022 08:00
Onsite Hours :07:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :Sunny
Departure Time :11/08/2022 15:00
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
11/08/2022 Test 1 23 88.0 3 99.4 21.3 88.5 95 D6938 Fail
Location : see attached Daily Field Report, Elv/Depth :1060
Comment : Area requires recompaction and retesting prior to continued fill placement Gauge Serial No. :
11/08/2022 test 2 17.3 111.3 3 99.4 21.3 112.0 95 D6938 Pass
Location : see attached Daily Field Report, Elv/Depth :1080
Comment : Gauge Serial No. :
11/08/2022 test 3 21 93.7 3 99.4 21.3 94.3 95 D6938 Fail
Location : see attached Daily Field Report, Elv/Depth :1070
Comment : Area requires recompaction and retesting prior to continued fill placement Gauge Serial No. :
Technician Signature / DateVidal Dias, November 8, 2022
Reviewer Name / DateKenneth Mosman, April 07, 2023