Density Test Report

Date :11/08/2022
Project No :2022C135
Client Company :Mark Spain
Arrival Time :11/08/2022 9:00
Onsite Hours :08:00
Name of the Project : Barnett Shoals Road Development
Project Location :Watkinsville
Weather :Sunny
Departure Time :11/08/2022 17:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
11/08/2022 1 17.1 106.7 P-3 108.2 18.7 98.6 95 D6938 Pass
Location : North of keyway, Elv/Depth :-6' from top of keyway
Comment : Gauge Serial No. :29588
11/08/2022 2 19.9 102.1 P-2 99.5 22.1 102.6 95 D6938 Pass
Location : South of keyway, Elv/Depth :-6' from top of keyway
Comment : Gauge Serial No. :29588
11/08/2022 3 24 98.2 P-2 99.5 22.1 98.7 95 D6938 Pass
Location : in keyway, Elv/Depth :-5.5' from top of keyway
Comment : Gauge Serial No. :29588
11/08/2022 4 24.6 98.9 P-2 99.5 22.1 99.4 95 D6938 Pass
Location : in keyway, Elv/Depth :-5.5' from top of keyway
Comment : Gauge Serial No. :29588
11/08/2022 5 24.9 97.7 P-1 97.3 23.7 100.4 95 D6938 Pass
Location : in keyway , Elv/Depth :-5' from top of keyway
Comment : Gauge Serial No. :29588
Technician Signature / DateAminullah Azimi, November 8, 2022
Reviewer Name / DateKenneth Mosman, November 13, 2022