Density Test Report

Date :11/10/2022
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :11/10/2022 08:00
Onsite Hours :04:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :
Departure Time :11/10/2022 12:00
ASEC Technician Name :Vidal Dias

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
11/10/2022 Test 1 21.1 90.5 2 95.0 23.5 95.3 95 D6938 Pass
Location : Lot #68 , Elv/Depth :1080
Comment : Gauge Serial No. :
11/10/2022 Test 2 20.1 91.6 2 95.0 23.5 96.4 95 D6938 Pass
Location : Lot #67, Elv/Depth :1075
Comment : Gauge Serial No. :
11/10/2022 Test 3 22.1 90.5 2 95.0 23.5 95.3 95 D6938 Pass
Location : Lot #66 , Elv/Depth :1075
Comment : Gauge Serial No. :
Technician Signature / DateVidal Dias, November 10, 2022
Reviewer Name / DateKenneth Mosman, April 07, 2023