Density Test Report

Date :01/20/2023
Project No :2022C227
Client Company :Artisan
Arrival Time :01/20/2023 8:30
Onsite Hours :06:30
Name of the Project :Riverwalk Manor (CMT) Unit 2, PH 4E and 4F
Project Location :Dallas
Weather :Sunny
Departure Time :01/20/2023 15:00
ASEC Technician Name :

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
01/20/2023 1 16.1 98.4 P-01 100.4 18.6 98.0 90 D6938 Pass
Location : Lot #422, Elv/Depth :-18' from finished grade
Comment : Gauge Serial No. :85759
01/20/2023 2 15.6 96.6 P-01 100.4 18.6 96.2 90 D6938 Pass
Location : at roadway, Elv/Depth :-18' from finished grade
Comment : Gauge Serial No. :85759
01/20/2023 3 15.3 92.7 P-01 100.4 18.6 92.3 90 D6938 Pass
Location : Lot #423, Elv/Depth :-18' from finished grade
Comment : Gauge Serial No. :85759
01/20/2023 4 15.1 95.6 P-01 100.4 18.6 95.2 90 D6938 Pass
Location : Lot #421, Elv/Depth :-18' from finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, January 20, 2023
Reviewer Name / DateKenneth Mosman, January 29, 2023