Density Test Report

Date :02/06/2023
Project No :2022C227
Client Company :Artisan
Arrival Time :02/06/2023 10:00
Onsite Hours :08:00
Name of the Project :Riverwalk Manor (CMT) Unit 2, PH 4E and 4F
Project Location :Dallas
Weather :Sunny
Departure Time :02/06/2023 18:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/06/2023 1 16.6 100.0 P-01 100.4 18.6 99.6 90 D6938 Pass
Location : Lot #422, Elv/Depth :-11' from finished grade
Comment : Gauge Serial No. :85759
02/06/2023 2 17.4 99.9 P-01 100.4 18.6 99.5 90 D6938 Pass
Location : at roadway, Elv/Depth :-6' from finished grade
Comment : Gauge Serial No. :85759
02/06/2023 3 16.9 99.1 P-01 100.4 18.6 98.7 90 D6938 Pass
Location : at roadway, Elv/Depth :-12' from finish grade
Comment : Gauge Serial No. :85759
02/06/2023 4 20.5 92.0 P-01 100.4 18.6 91.6 90 D6938 Pass
Location : at Lot #423, Elv/Depth :-7' from finish grade
Comment : Gauge Serial No. :85759
02/06/2023 5 17.3 101.9 P-01 100.4 18.6 101.5 95 D6938 Pass
Location : at Lot #421, Elv/Depth :-1' from finish grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 6, 2023
Reviewer Name / DateKenneth Mosman, February 12, 2023