Density Test Report

Date :04/24/2023
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :04/24/2023 10:00
Onsite Hours :07:30
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :cloudy
Departure Time :04/24/2023 17:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/24/2023 1 30.5 89.7 3 99.4 21.3 90.2 90 D6938 Pass
Location : 23 feet to SE of MH BB11, Elv/Depth :6 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/24/2023 2 27.7 97.0 3 99.4 21.3 97.6 90 D6938 Pass
Location : 110 feet to SE of MH BB1, Elv/Depth :5 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/24/2023 3 27.4 93.9 3 99.4 21.3 94.5 90 D6938 Pass
Location : 21 feet to SE of MH BB11, Elv/Depth :5.5 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/24/2023 4 28.8 90.8 3 99.4 21.3 91.3 90 D6938 Pass
Location : 178 feet to SW of MH BB11, Elv/Depth :4.5 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/24/2023 5 26.2 94.0 3 99.4 21.3 94.6 90 D6938 Pass
Location : 27 feet to SE of MH BB11, Elv/Depth :4.5 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/24/2023 6 26.2 93.7 3 99.4 21.3 94.3 90 D6938 Pass
Location : 110 feet to SE of MH BB11, Elv/Depth :4.5 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, April 24, 2023
Reviewer Name / DateKenneth Mosman, May 07, 2023