Density Test Report

Date :09/25/2023
Project No :2023C144
Client Company :CCG
Arrival Time :09/25/2023 8:00
Onsite Hours :08:00
Name of the Project :Carodel Farms @ Union Church Rd
Project Location :Flowery Branch
Weather :sunny
Departure Time :09/25/2023 16:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/25/2023 1 26.5 93.4 P-1 96.5 22.3 96.8 90 D6938 Pass
Location : Lot #106, Elv/Depth :3 feet below finished grade
Comment : Moisture content higher than optimum moisture (wet) Gauge Serial No. :85759
09/25/2023 2 22 92.3 P-1 96.5 22.3 95.6 90 D6938 Pass
Location : Lot #107, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
09/25/2023 3 22.4 95.9 P-1 96.5 22.3 99.4 90 D6938 Pass
Location : Lot #10, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
09/25/2023 4 23.2 94.6 P-1 96.5 22.3 98.0 90 D6938 Pass
Location : Lot #11, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
09/25/2023 5 23.3 94.4 P-1 96.5 22.3 97.8 90 D6938 Pass
Location : Lot #12, Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :85759
09/25/2023 6 23 111.5 P-1 96.5 22.3 94.0 90 D6938 Pass
Location : Lot #13, Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, September 25, 2023
Reviewer Name / DateKenneth Mosman, October 01, 2023