- Density Test Report Report ID: 63286
- Edit Download Report
Density Test Report
Date :12/08/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/08/2023 8:00
Onsite Hours :05:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :cloudy
Departure Time :12/08/2023 13:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
12/08/2023 | 1 | 21.2 | 96.9 | 24469 | 103.9 | 18.7 | 93.3 | 90 | D6938 | Pass |
Location : | Lot #30, Elv/Depth :2.5 below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
12/08/2023 | 2 | 17.8 | 98.7 | 24468 | 111.3 | 17.5 | 88.7 | 90 | D6938 | Fail |
Location : | Lot #29, Elv/Depth :2 feet below finished grade | |||||||||
Comment : | Recompaction and retesting required | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, December 8, 2023
Reviewer Name / DateKenneth Mosman, March 08, 2024