Skip to content

Density Test Report

Date :12/13/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/13/2023 10:30
Onsite Hours :03:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/13/2023 13:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
12/13/2023 1 17.9 107.2 24468 111.3 17.5 96.3 90 D6938 Pass
Location : Lot #29, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
12/13/2023 2 18.5 101.2 24468 111.3 17.5 90.9 90 D6938 Pass
Location : Lot #30, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, December 13, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024