- Density Test Report Report ID: 63313
- This project is inactive from admin.Download Report
Density Test Report
Date :12/13/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/13/2023 10:30
Onsite Hours :03:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/13/2023 13:30
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
12/13/2023 | 1 | 17.9 | 107.2 | 24468 | 111.3 | 17.5 | 96.3 | 90 | D6938 | Pass |
Location : | Lot #29, Elv/Depth :1 foot below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
12/13/2023 | 2 | 18.5 | 101.2 | 24468 | 111.3 | 17.5 | 90.9 | 90 | D6938 | Pass |
Location : | Lot #30, Elv/Depth :1 foot below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, December 13, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024