Density Test Report

Date :12/15/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/15/2023 9:00
Onsite Hours :04:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/15/2023 13:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
12/15/2023 1 18.9 99.4 24469 103.9 18.7 95.7 90 D6938 Pass
Location : 32 feet NE of MH B5,, Elv/Depth :4.5 feet below finished grade
Comment : Gauge Serial No. :85759
12/15/2023 2 15.1 98.3 24469 103.9 18.7 94.6 90 D6938 Pass
Location : 88 feet SW of MH B6., Elv/Depth :10 feet below finished grade
Comment : Gauge Serial No. :85759
12/15/2023 3 15.6 96.8 24469 103.9 18.7 93.2 90 D6938 Pass
Location : Lot #32, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :
12/15/2023 4 15.2 98.0 24469 103.9 18.7 94.3 90 D6938 Pass
Location : Roadway in the front of Lot #32., Elv/Depth :8 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, December 15, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024