Density Test Report

Date :12/18/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/18/2023 9:00
Onsite Hours :03:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/18/2023 12:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
12/18/2023 1 15.7 104.6 24468 111.3 17.5 94.0 90 D6938 Pass
Location : Lot #36, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
12/18/2023 2 15.8 100.3 24468 111.3 17.5 90.1 90 D6938 Pass
Location : Lot #37, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
12/18/2023 3 15.7 116.2 24468 111.3 17.5 90.2 90 D6938 Pass
Location : Lot #38, Elv/Depth :1.5 foot below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, December 18, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024