Density Test Report

Date :12/21/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/21/2023 13:30
Onsite Hours :02:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/21/2023 16:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
12/21/2023 1 16.5 101.5 24468 111.3 17.5 91.2 90 D6938 Pass
Location : at keyway of culvert, Elv/Depth :25 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, December 21, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024