Density Test Report

Date :01/02/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :01/02/2024 12:30
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :01/02/2024 16:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
01/01/2024 1 20.4 103.0 24468 111.3 17.5 92.5 90 D6938 Pass
Location : for roadway (location shows in picture), Elv/Depth :20 feet below finished grade
Comment : Gauge Serial No. :85759
01/01/2024 2 17.6 105.4 24468 111.3 17.5 94.7 90 D6938 Pass
Location : at roadway (location shown in picture) , Elv/Depth :25 feet below finished grade
Comment : Gauge Serial No. :85759
01/01/2024 3 16.5 100.7 24468 111.3 17.5 90.5 90 D6938 Pass
Location : at roadway (location shown in picture), Elv/Depth :18 feet below finished grade
Comment : Gauge Serial No. :
01/01/2024 4 17.9 98.0 24469 103.9 18.7 94.3 90 D6938 Pass
Location : Sewer trench, 20 feet SW of MH B5, Elv/Depth :5.5 feet below finished grade
Comment : Gauge Serial No. :85759
01/01/2024 5 19.8 100.0 24469 103.9 18.7 96.2 90 D6938 Pass
Location : Sewer trench, 118 feet SW of MH B5, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, January 2, 2024
Reviewer Name / DateKenneth Mosman, March 10, 2024