Skip to content

Density Test Report

Date :01/04/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :01/04/2024 9:00
Onsite Hours :03:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :01/04/2024 12:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
01/04/2024 1 19 105.5 24468 111.3 17.5 94.8 90 D6938 Pass
Location : at lot#32, Elv/Depth :8 feet below finish grade
Comment : Gauge Serial No. :85759
01/04/2024 2 18.7 104.3 24468 111.3 17.5 93.7 90 D6938 Pass
Location : Sower line, 31 feet to SE of MH B4,, Elv/Depth :4.5 feet below finish grade
Comment : Gauge Serial No. :85759
01/04/2024 3 18.5 104.4 24468 111.3 17.5 93.8 90 D6938 Pass
Location : 32 feet to NW of MH B5,, Elv/Depth :5.5 feet below finish grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, January 4, 2024