- Density Test Report Report ID: 63764
- This project is inactive from admin.Download Report
Density Test Report
Date :01/18/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :01/18/2024 13:00
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :cloudy
Departure Time :01/18/2024 17:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
01/18/2024 | 1 | 20.3 | 102.8 | 24468 | 111.3 | 17.5 | 92.4 | 90 | D6938 | Pass |
Location : | Water storm line, 67 feet SE of MH 2H, Elv/Depth :2 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/18/2024 | 2 | 16.8 | 101.5 | 24468 | 111.3 | 17.5 | 91.2 | 90 | D6938 | Pass |
Location : | Water storm line , 29 feet NW of MH 2H.2, Elv/Depth :3.5 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/18/2024 | 3 | 22 | 101.6 | 24468 | 111.3 | 17.5 | 91.3 | 90 | D6938 | Pass |
Location : | location shown in picture , Elv/Depth :16 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/18/2024 | 4 | 20.2 | 107.6 | 24468 | 111.3 | 17.5 | 96.7 | 90 | D6938 | Pass |
Location : | location shown in picture, Elv/Depth :19 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/18/2024 | 5 | 21.3 | 102.0 | 24468 | 111.3 | 17.5 | 91.6 | 90 | D6938 | Pass |
Location : | location shown in picture , Elv/Depth :14 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, January 18, 2024
Reviewer Name / DateKenneth Mosman, March 10, 2024