Density Test Report

Date :01/30/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :01/30/2024 9:00
Onsite Hours :07:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :01/30/2024 16:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
01/30/2024 1 17.3 102.4 24468 111.3 17.5 92.0 90 D6938 Pass
Location : 30 feet north of MH A3, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
01/30/2024 2 16.7 101.3 24468 111.3 17.5 91.0 90 D6938 Pass
Location : 22 feet south of MH A4, Elv/Depth :11 feet below finished grade
Comment : Gauge Serial No. :85759
01/30/2024 3 17.6 102.0 24468 111.3 17.5 91.6 90 D6938 Pass
Location : Trench under roadway (location shown pictures), Elv/Depth :13 feet below finished grade
Comment : Gauge Serial No. :85759
01/30/2024 4 16.1 102.8 24468 111.3 17.5 92.4 90 D6938 Pass
Location : Trench under roadway (location shown in pictures), Elv/Depth :13 feet below finished grade
Comment : Gauge Serial No. :85759
01/30/2024 5 14.7 101.3 24468 111.3 17.5 91.0 90 D6938 Pass
Location : Trench under roadway (location shown in pictures), Elv/Depth :11 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, January 30, 2024
Reviewer Name / DateKenneth Mosman, March 10, 2024