Density Test Report

Date :02/02/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :02/02/2024 13:00
Onsite Hours :03:30
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :sunny
Departure Time :02/02/2024 16:30
ASEC Technician Name :

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/02/2024 1 23.3 94.6 4 98.6 20.2 95.9 90 D6938 Pass
Location : lot#51, Elv/Depth :finished grade
Comment : Gauge Serial No. :85759
02/02/2024 2 26.2 97.7 4 98.6 20.2 99.1 90 D6938 Pass
Location : lot#50, Elv/Depth :finished grade
Comment : Gauge Serial No. :85759
02/02/2024 3 28.3 89.6 4 98.6 20.2 90.9 90 D6938 Pass
Location : lot#20, Elv/Depth :2 feet below finish grade
Comment : Gauge Serial No. :85759
02/02/2024 4 26.9 89.2 4 98.6 20.2 90.5 90 D6938 Pass
Location : lot#19, Elv/Depth :2 feet below finish grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 2, 2024