- Home
- Density Test Report Report ID: 63985
- Edit Download Report
Density Test Report
Date :02/05/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/05/2024 11:30
Onsite Hours :03:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/05/2024 15:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
02/05/2024 | 1 | 17.4 | 103.1 | 24468 | 111.3 | 17.5 | 92.6 | 90 | D6938 | Pass |
Location : | Creek crossing , Elv/Depth :7 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85758 | |||||||||
02/05/2024 | 2 | 15.5 | 101.6 | 24468 | 111.3 | 17.5 | 91.3 | 90 | D6938 | Pass |
Location : | Creek crossing, Elv/Depth :5.5 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
02/05/2024 | 3 | 15.1 | 102.0 | 24468 | 111.3 | 17.5 | 91.6 | 90 | D6938 | Pass |
Location : | Creek crossing, Elv/Depth :8 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, February 5, 2024
Reviewer Name / DateKenneth Mosman, March 11, 2024