Density Test Report

Date :02/06/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/06/2024 11:30
Onsite Hours :03:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/06/2024 15:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/06/2024 1 16.4 103.2 24468 111.3 17.5 92.7 90 D6938 Pass
Location : Sewer pipe trench, 22 feet SW of MH B1 , Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :85759
02/06/2024 2 18.9 106.9 24468 111.3 17.5 96.0 90 D6938 Pass
Location : Creek crossing (location shown in pictures), Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
02/06/2024 3 21.1 101.6 24468 111.3 17.5 91.3 90 D6938 Pass
Location : Creek crossing (location shown in pictures), Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :85759
02/06/2024 5 18.7 101.1 24468 111.3 17.5 90.8 90 D6938 Pass
Location : Creek crossing (location shown in pictures), Elv/Depth :7 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 6, 2024
Reviewer Name / DateKenneth Mosman, March 11, 2024