Density Test Report

Date :02/08/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/08/2024 11:30
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/08/2024 15:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/08/2024 1 15 103.1 24468 111.3 17.5 92.6 90 D6938 Pass
Location : Sewer pipe trench, 16 feet SW of MHB1, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
02/08/2024 2 18.2 101.6 24468 111.3 17.5 91.3 90 D6938 Pass
Location : Sewer pipe trench, 20 feet NE of MH A4, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
02/08/2024 3 16.2 110.3 24468 111.3 17.5 99.1 90 D6938 Pass
Location : Sewer pipe trench, 75 feet south of MH A9, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
02/08/2024 4 15.7 108.4 24468 111.3 17.5 97.4 90 D6938 Pass
Location : 135 feet to North of MH A8,, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
02/08/2024 5 15.7 106.9 24468 111.3 17.5 96.0 90 D6938 Pass
Location : 51 feet north of MH A8, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
02/08/2024 6 18.6 107.7 24468 111.3 17.5 96.8 95 D6938 Pass
Location : Lot #25, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 8, 2024
Reviewer Name / DateKenneth Mosman, March 11, 2024