Density Test Report

Date :02/09/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/09/2024 10:00
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :cloudy
Departure Time :02/09/2024 14:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/09/2024 1 14.8 100.7 24468 111.3 17.5 90.5 90 D6938 Pass
Location : 23 feet SW of MH A4, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :85759
02/09/2024 2 16.1 105.6 24468 111.3 17.5 94.9 90 D6938 Pass
Location : 33 feet west of MH A5, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :85759
02/09/2024 3 16.5 100.3 24468 111.3 17.5 90.1 90 D6938 Pass
Location : 26 feet east of MH A6, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :85759
02/09/2024 4 16.7 100.6 24469 103.9 18.7 96.8 95 D6938 Pass
Location : Lot #32, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
02/09/2024 5 16.3 100.7 24469 103.9 18.7 96.9 95 D6938 Pass
Location : Roadway in the front of Lot #25, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
02/09/2024 6 16 102.1 24469 103.9 18.7 98.3 90 D6938 Pass
Location : Lot #25, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 9, 2024
Reviewer Name / DateKenneth Mosman, March 11, 2024