Density Test Report

Date :02/16/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :02/16/2024 8:30
Onsite Hours :04:30
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :sunny
Departure Time :02/16/2024 13:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/16/2024 1 31.2 85.6 2 95.0 23.5 90.1 95 D6938 Fail
Location : Lot #23, Elv/Depth :7 feet below finished grade
Comment : Moisture content well above 3 percent over optimum Gauge Serial No. :85759
02/16/2024 2 28.5 86.5 1 83.2 25.3 104.0 95 D6938 Pass
Location : Roadway in front of Lot #24, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :85759
02/16/2024 3 27.6 85.6 1 83.2 25.3 102.9 95 D6938 Pass
Location : Basement of Lot #24, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 16, 2024
Reviewer Name / DateKenneth Mosman, March 12, 2024