Density Test Report

Date :02/16/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/16/2024 13:00
Onsite Hours :03:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/16/2024 16:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/16/2024 1 19 102.1 24468 111.3 17.5 91.7 90 D6938 Pass
Location : Sewer pipe, 18 feet south of MHA7, Elv/Depth :7 feet below finished grade
Comment : Gauge Serial No. :85759
02/16/2024 2 19.2 101.2 24468 111.3 17.5 90.9 90 D6938 Pass
Location : Sewer pipe, 31 feet north of MH A6, Elv/Depth :8 feet below finished grade
Comment : Gauge Serial No. :85759
02/16/2024 3 19.2 101.2 24469 103.9 18.7 97.4 95 D6938 Pass
Location : Lot #29, Elv/Depth :6 inches below finished grade
Comment : Gauge Serial No. :85759
02/16/2024 4 19.2 100.6 24469 103.9 18.7 96.8 95 D6938 Pass
Location : Lot #30, Elv/Depth : 6 inches below finish grade
Comment : Gauge Serial No. :85759
02/16/2024 5 15.5 108.9 24468 111.3 17.5 97.8 95 D6938 Pass
Location : Roadway in front of Lot #30, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
02/16/2024 6 19.8 101.0 24469 103.9 18.7 97.2 95 D6938 Pass
Location : Lot #32, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
02/16/2024 7 19.1 102.9 24469 103.9 18.7 99.0 90 D6938 Pass
Location : Lot #25, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 16, 2024
Reviewer Name / DateKenneth Mosman, March 12, 2024