Density Test Report

Date :02/21/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/21/2024 15:00
Onsite Hours :02:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/21/2024 17:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/21/2024 1 16.8 102.2 24209 111.6 16.5 91.6 90 D6938 Pass
Location : 35 feet NE of MH A7, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :85759
02/21/2024 2 16.6 104.7 24209 111.6 16.5 93.8 90 D6938 Pass
Location : 53 feet SW of MH A8, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 21, 2024
Reviewer Name / DateKenneth Mosman, March 15, 2024