- Density Test Report Report ID: 64421
- This project is inactive from admin.Download Report
Density Test Report
Date :02/23/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/23/2024 13:00
Onsite Hours :02:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :cloudy
Departure Time :02/23/2024 15:30
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
02/23/2024 | 1 | 18.2 | 106.6 | 24468 | 111.3 | 17.5 | 95.8 | 95 | D6938 | Pass |
Location : | Lot #33, Elv/Depth :16 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
02/23/2024 | 2 | 19.3 | 104.3 | 24469 | 103.9 | 18.7 | 100.4 | 95 | D6938 | Pass |
Location : | Lot #34, Elv/Depth :9 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, February 23, 2024
Reviewer Name / DateKenneth Mosman, March 16, 2024