Density Test Report

Date :02/24/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/24/2024 12:00
Onsite Hours :03:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/24/2024 15:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/24/2024 1 16.7 102.4 24469 103.9 18.7 98.6 95 D6938 Pass
Location : Lot #33, Elv/Depth :15 feet below finished grade
Comment : Gauge Serial No. :85759
02/24/2024 2 16.7 101.5 24469 103.9 18.7 97.7 95 D6938 Pass
Location : Basement of Lot #33, Elv/Depth :8 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 24, 2024
Reviewer Name / DateKenneth Mosman, March 16, 2024