Density Test Report

Date :02/26/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/26/2024 15:00
Onsite Hours :02:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/26/2024 17:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/26/2024 1 18.5 104.1 24469 103.9 18.7 100.2 95 D6938 Pass
Location : Lot #33, Elv/Depth :13.5 feet below finished grade
Comment : Gauge Serial No. :85759
02/26/2024 2 20.3 101.3 24469 103.9 18.7 97.5 95 D6938 Pass
Location : Lot #33 basement, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :85759
02/26/2024 3 16.5 100.5 24468 111.3 17.5 90.3 90 D6938 Pass
Location : Between MH 2B and MH 2B.1, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :85759
02/26/2024 4 16.5 100.6 24468 111.3 17.5 90.4 90 D6938 Pass
Location : Water storm, 33 feet NW of MH 2B, Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 26, 2024
Reviewer Name / DateKenneth Mosman, March 16, 2024